UPS nJoy Garun 10KL 10KVA/10KW
179.990,00 ден
Гаранција 24 месеци, 12 месеци на батериите
- Опис
Опис
Phase
Single Phase
3 Phase In – 1 Phase Out
3 Phase In – 3 Phase Out
Technology
On-line (VFI)
Typology
Tower
Output waveform
Pure Sine Wave
Power
10KVA / 10KW
Input Nominal Voltage
3 x 400 VAC (3Ph+N) / 1 x 230 VAC (Ph+N)
Output Power Factor
1.0
Output Nominal Voltage
3 x 360*/380/400/415 VAC (3Ph+N)
1 x 208*/220/230/240 VAC (Ph-N)
Input Voltage Range
3:3 phase
190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load
3:1 phase or single phase
110-300 VAC (1-phase) @ 50% load
176-276 VAC (1-phase) @ 100% load
Input Nominal Frequency
46 ~ 54Hz
Output Voltage Precision
± 1% (Battery mode)
Batteries Presence
Internal and / or External
Batteries Installed
No batteries installed
20 pcs of 12V9Ah or 12V7Ah type batteries supported
Outlets
Terminal Block Wiring
Efficiency
up to 98.5 % in Eco mode
LCD Display
Yes (touch screen)
Communication Ports
RS232
USB
SNMP
EPO
Parallel operation
up to 3 units
Generator Compatible
Yes
Noise Level
<60dB
Features
Smart battery charger to optimize batteries’ performance
Adjustable batteries design
Optional isolation transformer*
DSP technology guarantees high performance
Active power factor correction in all phases
Maintenance bypass
5” large touch LCD display
Power management over SNMP / Modbus / AS 400 card
ECO mode operation for energy saving
Dimensions (L x W x H)
630 x 250 x 750 mm
Weight
44.5 kg (without batteries)
Remarks
*For detailed specs please check product datasheet